Model No. | Rated Current | Turns Ratio | Output Current | Load | Insulation Voltage | Phase Error | Accuracy | |
AC | DC | |||||||
DCT006 | 6A | 4.3 A | 1:2500 | 2.4mA | 10Ω/20Ω | >4kV/1min | <15' | 0.1 Class |
DCT100 | 40 A | 28A | 16mA | 12.5Ω | >4kV/1min | <15' | 0.1 Class | |
DCT101 | 60 A | 43 A | 24mA | 12.5Ω | >4kV/1min | <15' | 0.1 Class | |
DCT102 | 80A | 60A | 32mA | 12.5Ω | >4kV/1min | <15' | 0.1 Class | |
DCT103 | 100 A | 71A | 40mA | 12.5Ω | >4kV/1min | <15' | 0.1 Class | |
DCT104 | 120 A | 85 A | 48mA | 12.5Ω | >4kV/1min | <15' | 0.1 Class | |
DCT150 | 150A | 106A | 60mA | 12.5Ω | >4kV/1min | <15' | 0.1 Class | |
DCT 200A | 200A | 145A | 50mA | 10Ω | >4kV/1min | <15' | 0.1 Class | |
DCT 200B | 200A | 145A | 60mA | 10Ω | >4kV/1min | <15' | 0.1 Class |
Model No. | A | B | C | Secondary Wire |
DCT006 | 10±1 | 30±1 | 18±1 | UL1007 80℃ 300V UL1015 105℃ 600V AWG18-28 |
DCT100 | 8±1 | 30±1 | 18±1 | |
DCT101 | 8±1 | 30±1 | 18±1 | |
DCT102 | 10±1 | 32±1 | 21±1 | |
DCT103 | 10±1 | 33±1 | 24±1 | |
DCT104 | 10±1 | 33±1 | 24±1 | |
DCT150 | 12±1 | 39±1 | 20±1 | |
DCT200A | 12±1 | 39±1 | 24±1 | |
DCT200B | 16±1 | 40±1 | 24±1 |
★Dielectric Strength: not less than 4kV/1mA/1min.
★Insulation Resistance: >500MΩ (500VDC).
★Operating Temperature : -40℃~ +85℃.
★Relative Humidity: ≤95% ( 25℃) Altitude: ≤10000m.
★ AC measurement capacity is 20% higher than rated current.
★ High Precision. suitable for kWh meter Class 0.2, Class 0.5, Class 1.0.
★ Typical AC current measurement error is within 0.02% at Ib test point.
★ Typical phase shift is at 1-10' , additional compensation is not needed.
★ Very reliable and stable performance at different temperature conditions.
★ Good linearity, it support automatically software calibration.
★ Different type for different fixing and assembly easily.
★ Quick connection to PCB available on request.